Coastal electrics, done properly, first time.5% off for pensioners 07763 100 477 · hello@margateelectrical.co.uk
Margate & ElectricalOld Town · Cliftonville · Westbrook · CT9

Guides · 2026-11-16

Can I put a socket in the bathroom?

Not an ordinary one. Under BS 7671:2018+A2:2022, a normal 13A socket is not allowed in a room that contains a bath or shower, and the only mains outlet you can usually have is a shaver supply unit. Everything else, from hairdryers to phone chargers, needs a socket in the next room or a different solution.

The quick answer, by what you want to plug in

What you wantUsually allowed?What to do instead
Electric shaver or toothbrush chargerYesA shaver supply unit to BS EN 61558-2-5, fitted by an electrician.
Hairdryer or straightenersNo standard socketUse a socket in the bedroom or landing, away from the bath or shower.
Heated towel railNot by plugFixed wiring through a fused spur, switched, by an electrician.
Extractor fanNot by plugFixed, correctly rated fan on a protected supply.
Phone or tablet chargingNoKeep chargers outside the bathroom.
Washing machineNot in a bathroom with a bath or showerPut it in the kitchen or utility, or ask an electrician about a suitable position.

Why the rule exists

Water and electricity are the whole problem. Wet skin, steam, metal pipework and a bare floor all lower your resistance to a shock, and a plug being pulled with wet hands is exactly the situation the rule is built around. Section 701 of BS 7671 covers rooms with a bath or shower, and it is deliberately strict. A pull cord for the light, a shaver unit and fixed, correctly rated fittings are the normal answer.

Zones, in plain English

Section 701 divides a bathroom into zones around the bath or shower. Zone 0 is inside the bath or shower tray, Zone 1 is the space directly above it, and Zone 2 is the band beside it. Any fitting in those areas needs a suitable IP rating, and general sockets are not permitted. The exact dimensions depend on whether there is a bath, a shower with a tray, or a walk-in enclosure, so an electrician measures the actual room rather than guessing. The same section requires 30mA RCD protection for the circuits serving the room.

Shaver unit, not a socket

A shaver supply unit contains an isolating transformer, so the outlet is separated from the mains supply. That is why it is allowed where a normal socket is not. A cheap shaver socket sold without that standard marking is not the same thing, so ask your electrician which unit they are fitting.

What you can do yourself, and what you cannot

Safe for a homeowner

Needs a registered electrician

New circuits and work in a bathroom are generally notifiable in England under Part P, so it must be done and certified by someone registered to do so. Do not do live work yourself, and do not unscrew a socket cover to see what is behind it.

Where a socket can go

The restriction is about the room with the bath or shower. A socket in an adjoining bedroom, landing or hallway is a separate matter and is normal, provided it sits away from the wet areas. If your bathroom is a large room with a bath at one end and a basin at the other, or you have an en-suite, ask for the layout to be assessed on site rather than relying on a rule of thumb. Our guide to adding extra sockets to a room explains the options for the room next door, and fused spurs covers fixed supplies such as extractor fans.

Warning signs in an existing bathroom

Any of these is worth getting looked at. A landlord's EICR will record bathroom installation faults against a code, and an old socket in the room is likely to be flagged.

Margate bathrooms

Many older Margate houses, including terraces in Old Town and large Cliftonville properties split into flats, have bathrooms that were added later, often squeezed into a former bedroom or a rear extension. They tend to be small, damp and short of sockets, which tempts people into leads and adaptors. A small room with no extractor and a coastal damp problem is exactly where good fixed fittings matter most. Where the plaster is original, we usually route cable in surface trunking or through a neighbouring wall rather than damaging the walls. Check the structure of the home and any listed or conservation status before changing visible fittings.

Getting it sorted

Send a photo of the bathroom and the nearest socket on the landing or in the next room, with a line about what you want to plug in, through our contact page. We will tell you what is allowed and what the safest layout is.

Common questions

Can I have a shaver socket in the bathroom?

Yes, if it is a shaver supply unit to BS EN 61558-2-5 fitted by a registered electrician. It is the one mains outlet the regulations normally allow in a room with a bath or shower.

Can I put a hairdryer socket in the bathroom?

Not a standard socket. Use a socket in the bedroom or landing, away from the bath and shower, and keep the lead short and dry.

Do bathroom circuits need an RCD?

Yes. Circuits serving a room with a bath or shower should have 30mA RCD protection, and you should test it using the button on the consumer unit every few months.

Need this done on your property?

Photos, postcode and a short description to hello@margateelectrical.co.uk or WhatsApp 07763 100 477. Same-day fixed quote.